Controls 4 Steam UK Limited


Solids Content

TDS 1
PVC 5
Automatic Timed Bottom Blowdown and Manual Valves Installed in Series
Aquanet's AQTDS Surface (TDS) Blowdown Controller, has three independent outputs.
1) Temperature compensated Surface (TDS) Blowdown for higher accuracy and tighter control band
2) Timed Bottom Blowdown Control with alarm outputs enabling automation of boiler bottom blowdown valve with easy to set time delay in hours and opening duration in seconds.
3) Freely configurable pulsed output control for slow opening of automatic steam isolation valve with alarm outputs

As we generate steam, the water in the boiler evaporates and the concentration of dissolved and suspended solids increases. How quickly they increase depends on the quality and condition of the feedwater. If we do nothing about this, the Dissolved Solids level will increase until we get foaming and priming with consequent problems within the boiler and the steam distribution system. It is essential therefore, that the dissolved solids level within steam boilers is not allowed to rise above a specified concentration.

The majority of boilers nowadays have automatic controls which monitor and regulate the solids content to within the boiler manufacturers specified limits to prevent foaming and carry over. However, the majority of controllers installed rely on a fixed temperature input to calculate the solids level. Since conductivity varies with temperature at approximately 2%/Deg.C accurate control can only be achieved when temperature compensation is automatically applied.

The suspended solids, which may otherwise form sludge, should be controlled by manual or automatic operation of the bottom blowdown valve. The most effective and economic way is to open the valve quickly but for short periods of 3 to 5 seconds duration. The object being to disturb the sludge at the bottom of the boiler and draw it out through the valve, short sharp operation has overtime proved the best method.

© 2012 by Controls 4 Steam UK Ltd. All rights reserved.
http://www.controls4steam.co.uk/case-studies/feedwater-treatment/the-solution/solids-content.html

Page updated 27th Aug 2010, 11:30

Designed and Maintained by Brick technology Ltd.